CX8 8-zone conventional detection panel
8-zone conventional detection panel with touchscreen display, USB/Bluetooth/Ethernet/WiFi/4G.
8-zone conventional detection panel, up to 32 devices per zone, distinguishing manual call point and detector alarms; 2.7″” multilingual TFT touchscreen with log of up to 10,000 events; 2 supervised programmable 24 V I/O. 300 mA. 2 independent relay outputs for alarm/fault.
Configuration and commissioning via on-board USB and/or Bluetooth without the need for additional cards. Communications for remote management and Nusku® platform access via included Ethernet and Wi-Fi ports, with an optional 4G module (ref. W4G). MODBUS protocol available via Ethernet port.
White RAL 9010 ABS plastic enclosure for surface or flush mounting. Dimensions: 360 mm x 400 mm x 100 mm. CPR certified EN54-2, EN54-4, EN54-13 and EN54-21. Requires two 12 V/7 Ah batteries (not included).