Algorithmic Detection Panels
Showing all 5 resultsSorted by latest
LX1C 1-Loop Algorithmic Detection Panel
1-loop algorithmic detection panel with capacity for up to 120 devices. USB/Bluetooth/Ethernet/WiFi/4G touchscreen display.
1-loop algorithmic detection panel with capacity for up to 120 devices, 2.7″ multi-language TFT touchscreen display with logging for up to 10,000 events, 2 programmable supervised 24V I/O. 300mA. 2 independent relay outputs for alarm/fault.
Configuration and commissioning via on-board USB and/or Bluetooth port, no additional card required. Communications for remote management and access to the Nusku® platform via included Ethernet and Wi-Fi ports, and optionally with a 4G module (ref. W4G). MODBUS protocol available via Ethernet port.
White RAL 9010 ABS plastic housing for surface or flush mounting. Dimensions: 200mm x 290mm x 80mm. CPR EN54-2, EN54-4, EN54-13, and EN54-21 certified. Two 12V/2Ah batteries required, not included.
LX1 1-Loop Algorithmic Detection Panel
1-loop algorithmic detection panel with capacity for up to 250 devices. USB/Bluetooth/Ethernet/WiFi/4G touchscreen display.
1-loop algorithmic detection panel with capacity for up to 250 devices, a 2.7″ multi-language TFT touchscreen display with up to 10,000 event logs, and 2 supervised 24V programmable I/O. 300mA. 2 independent relay outputs for alarm/fault. Configuration and commissioning via onboard USB and/or Bluetooth port, no additional card required.
Communications for remote management and access to the Nusku® platform via included Ethernet and Wi-Fi ports, with optional 4G module (ref. W4G). MODBUS protocol available via Ethernet port.
White RAL 9010 ABS plastic enclosure for surface or flush mounting. Dimensions: 360 mm x 400 mm x 100 mm. CPR certified EN54-2, EN54-4, EN54-13 and EN54-21. Requires two 12 V/7 Ah batteries (not included).
1-Loop Algorithmic Detection Panel BX1-2PRO
1-Loop algorithmic detection panel, expandable to 2, with capacity for up to 350 devices per loop. USB/Bluetooth/Ethernet/WiFi/4G touchscreen display.
1-Loop algorithmic detection panel, expandable to 2 loops via loop card (ref. TLBX), with capacity for up to 350 devices per loop, with connection to NETCOM® panel network via network card (Ref. T-NETCOM), 2.7″ multi-language TFT touchscreen display with logging of up to 10,000 events, 2 supervised 24V programmable I/O. 300mA. 2 independent relay outputs for alarm/fault.
Configuration and commissioning via USB port and/or onboard Bluetooth without the need for an additional card. Communications for remote management and access to the Nusku® platform via included Ethernet and Wifi ports, and optionally with a 4G module (ref. W4G). MODBUS protocol available via Ethernet port.
White RAL 9010 ABS plastic enclosure for surface or flush mounting. Dimensions: 360 mm x 400 mm x 100 mm. CPR certified EN54-2, EN54-4, EN54-13 and EN54-21. Requires two 12 V/7 Ah batteries (not included).
BX1-4MAX 1-loop algorithmic detection panel
1-loop algorithmic detection panel, expandable to 4 loops, with capacity for up to 350 devices per loop. Touchscreen display and removable graphic tablet. USB/Bluetooth/Ethernet/Wi-Fi/4G.
1-loop algorithmic detection panel, expandable to 4 loops via loop card (ref. TLBX), with capacity for up to 350 devices per loop, featuring NETCOM® panel network connection via network card (Ref. T-NETCOM), a 2.7″ multi-language TFT touchscreen display with logging for up to 10,000 events, and a removable 10″ graphic tablet for system configuration, graphic management, and interface with the Nusku® platform.
Configuration and commissioning via on-board USB and/or Bluetooth, no additional card required. 2 supervised programmable 24V I/O. 300mA. 2 independent relay outputs for alarm/fault. Communications for remote management and access to the Nusku® platform via included Ethernet and Wi-Fi ports, and optionally with a 4G module (ref. W4G). MODBUS protocol available via Ethernet port.
RAL 7035 gray metallic casing for surface or flush mounting. Dimensions: 490 mm x 420 mm. x 100mm. CPR EN54-2, EN54-4, EN54-13, and EN54-21 certified. Four 12V/7Ah batteries required, not included.
“
LX2 2-loop algorithmic detection panel
2-loop algorithmic detection panel with capacity for up to 250 devices per loop. USB/Bluetooth/Ethernet/Wi-Fi/4G touch display.
2-loop algorithmic detection panel with capacity for up to 250 devices per loop, 2.7″ multi-language TFT touch screen with a log of up to 10,000 events, and 2 supervised 24V programmable I/Os. 300mA. 2 independent relay outputs for alarm/fault.
Configuration and commissioning via on-board USB and/or Bluetooth without the need for an additional card. Communications for remote management and access to the Nusku® platform via included Ethernet and Wi-Fi ports, and optionally with a 4G module (ref. W4G). MODBUS protocol available via Ethernet port.
White RAL 9010 ABS plastic housing for surface or flush mounting. Dimensions 360mm. x 400mm. x 100mm. CPR EN54-2, EN54-4, EN54-13, and EN54-21 certified. Two 12V/2Ah batteries required, not included.